Operation Manual of WEICHAI GENSET
the direct sparking (short circuit test)
maintenance-free batteries: The
method because this will damage the
charging method is basically the same
battery.
as that for ordinary batteries. The
4) Always add distilled water
regularly for ordinary lead-acid
batteries. It is preferred to properly
charge dry-charged batteries before
use. For maintenance-free batteries for
which water can be added, proper
maintenance by adding necessary
distilled water at due time helps to
extend their service life.
5) Make sure that the air vent in the
battery cover is unblocked. When a
battery is charged, many air bubbles
will be produced. If the air vent is
blocked, the air cannot escape; when
the internal pressure increases to a
certain extent, the battery case will
burst.
6) Yellow-white paste will be found
around the battery poles and cap
occasionally; this is the result of the
voltage of each cell shall be limited to
2.3-2.4V during charging. The
conventional charging method will
consume more water, and the charging
current should be slightly lower (below
5A) for charging. If possible, the
maintenance-free battery can be
charged with charging equipment with
current-voltage characteristics. The
equipment can not only ensure full
charge, but also avoid overcharging
and consuming more water.
3) Scrapping indication: When the
hydrometer of maintenance-free
battery indicates light yellow or red, it
means that the battery is nearly
scrapped, and even if it is recharged, it
will discharge very quickly. Charging at
this time is only an emergency
expedient.
root column, line clamp and/or fixed
frame corroded by sulfuric acid. These
Lubrication of alternator bearing
substances have high resistance and
must be removed in time.
The alternator bearings are of
7) When it is necessary to use two
batteries connected in series, their
completely closed type and do not
need grease.
capacities should be the same
For general applications, if, the
preferably. Otherwise, the battery
vibration does not exceed the specified
service life will be affected.
value of BS5000-3 or ISO8528-9, and
2. Precautions for maintenance-free
battery
the ambient temperature does not
exceed 50℃, the following estimated
values can be used as reference for
1) Storage: The maintenance-free
planning bearing replacement.
battery can be stored for 10 months
from delivery to use, and its voltage
Definition in BS5000-3:
and capacitance will remain
The alternator shall be able to
unchanged.
withstand linear vibration with
2) Supplementary charging of
amplitude of 0.25 mm between 5 Hz
and 8 Hz and vibration with speed of
78