If the OP status column doesn’t show OP, the communication is not connected; if PO-Crc or P0-PHY
has a non-zero value in any column, it means the slave is interfered with, and if the value is large, it
means the communication is broken. You need to find the appropriate slave to observe if it is a wiring
alignment problem, or a hardware or network cable problem.
Note: All network cables, encoder cables and sensor cables on the amplifier should not be tied
together with the power cable.
If the servo is connected to the servo through the network cable, and the communication interruption
between the servo is detected, check whether the network cable between the servo and the servo is well
connected, and whether the connection between the crystal head of the network cable and the servo is
well connected and loose.
Wiring Precautions:
(1.) Confirm that the site of the electrical control cabinet is well grounded. Resistance within 10 ohms,
the smaller the better (preferably can be installed independent ground stake, only for laser cutting
machine)
(2.) Low voltage and high voltage cables need to be separated. Don’t entangle each other Network cable
connection display indication
EtherCAT Interface / Ethernet Interface