XC3000S Series Laser Cutting
System Commissioning Manual
6.3.1 Host cannot enter the system
1. Confirm that the host and monitor 220V power supply is normal, and use the universal
measurement host input power. The standard host power supply is DC12V.
2. Reboot the host to observe if it can enter the host interface normally.
3. Program run-down for abnormal system problems. The system is equipped with a one-key restore
system function: one-key (OneKEY) to restore in the boot page.
6.3.2 Enter the system sheet showing that the slave is not connected or not
in OP status
1. Check whether the network cable order is connected as required, and the connection order please
refer to (1.2 System Composition and Connection Order).
2. Check the network cable and the board for bad contact.
6.3.3 Software interface to view slave communication status
If you encounter communication interruptions, check the following steps: Find the "Hardware" button
on the left side of the main screen, and click on it to refer to the communication problems.
136
    "