2. Wiring and Connection
2.4.1 Power Unit Wiring (100W~3.5kW)
Note
Servo Drive
DC Reactor
Encoder
Note External
Regenerative
Resistance
Note 1)Please press the ON switch for the main power for at least 2 seconds, as the alarm signal input
takes 1~2 seconds after the main power is turned on.
Note 2)100[W]~400[W]drive has built-in recovery resistance of 50[W], 100[Ω]; 800[W]~1[kW]drive has
100[W], 40[Ω]; and 2[kW]~ 3.5[kW]drive has 150[W], 13[Ω] recovery resistance. Please use them
by shorting terminals B and BI. If the recovery resistance is high due to frequent
acceleration/deceleration, please open the shorting pins (B, BI) and connect external recovery
resistance to B, B+.
Note 3)Please peel off the 7~10[mm] of the sheath of the power cable to be used for the power unit as
shown in the figure below. And use the dedicated pressure terminal (see “2.4.2 Power Circuit
Electronics Specifications”)
Note 4)When removing power unit wiringfrom 100[W]~1[kW] drive, remove or connect it after pressing
the button at the drive’s terminal block. In case of 2[kW]~3.5[kW] drive, remove or connect it using
a flat-head driver.
2-7
    "