10. Application Functions
10.11.2 Using External Regeneration brake resistor
When using an external regeneration brake under consideration of the operation
environment, you should set the brake in the following order.
1. Externalregeneration brakewiring
- Connect the external regeneration brake to the B, B+ terminal.
- Remove shorts from B, BI terminals (default short at the time of release from the
factory, 1kW or less)
Extebrrnaaklerergeesnisetor생외ar t저부ion
L1
L2
L3
N
PO
PI
B+
B
BI
C1
C2
Wiring forexnternal regenerationbrakeesistor
B BI B+
2. Regeneration brakesetting (0x2009)
- Select the external regeneration brake (0x2009=1)
- Select this when connecting a regeneration brake with power larger than the internal
regeneration brake
3. Regeneration brake value setting (0x200B)
- Set the resistance value of the regeneration brakeregeneration brake to [Ω]Unit
- The value should be set if the regeneration brakesetting (0x2009) is 1.
- Default value: 0
10-41
    "