4 • STANDARD CONFIGURATION MENU
CFG
Setting Parameters
Configurat.
Default Custom
0 S.tv
Enable
selftuning,
autotuning,
softstart
S.tu Autotuning Selftuning Softstart
continuous
0
NO
NO
NO
1
YES
NO
NO
2
NO
YES
NO
3
YES
YES
NO
4
NO
NO
YES
Proportional heating
10.0
h.Pb
range or hysteresis in
regulation ON/OFF
0 ... 999,9% f.s.
4.0
h.It
Integral heating time
0,00 ... 99,99 min
1.0
h.dt
Derived heating time
0,00 ... 99,99 min
100.0
h.P.X Maximum limit heating
power
0,0 ... 100,0%
-1
xy.i Hysteresis for alarm 1
± 999
scale points
InP
Configurat.
Default Custom
22 (tr
Input settings
Control type
[0...11]
See table on InP
menu
0
tyP
Type of sensor, signal
and main input scale
See table on InP
menu
0
dP.S
Position of decimal point
for main input scale
dP.S
0
1
Format
xxxx
xxx.x
2
xx.xx (*)
3
x.xxx (*)
0
Lo.S
Minimum limit of main
input scale
min...max of input
selected in tyP
1000
xI.S
Maximum limit of main
input scale
min...max of input selected
in tyP
Out
Configurat.
Default Custom
0 aI.t
Output settings
Alarm type 1
See table on Out
menu
0
r.o.1
OUT 1
Attribution of
r.o.x MAIN logic output function, relay (OUT1)
0 HEAT (heating control output)
reference signal: 1 COOL (cooling control output)
HEAT, COOL,
2 AL1 - alarm 1
AL1, AL2, AL3
3 AL2 - alarm 2
4 AL3 - alarm 3 [A.Hb mod. 401])
5 -
2
r.o.2
OUT 2
Attribution of
reference signal:
HEAT, COOL,
AL1, AL2, AL3
6 LBA - alarm LBA
7 (AL1) OR (AL2)
8 (AL1) OR (AL2) OR (AL3 [A.Hb mod. 401])
9 (AL1) AND (AL2)
10 (AL1) AND (AL2) AND (AL3 [A.Hb mod. 401])
+ 16 for logic level denied at output
10
(t.1
Cycle time OUT1 relay or
logic = HEAT or COOL
0. ... 200 sec
81503D_MHW_400-401_12-2010_ENG
9