2.2 Nameplate Information
Nameplate
Description ofACMotor Drive Model:
DZB300 B 0015 L 4 A
Description of Serial Number::
06 10 8888
Production number
Production month
Production year
Chapter 2 Product Introduction
DZB Series
Fuling Inve r te r Use r Ma nua l - slide pdf.c om
Chapter 3 Mechanical and Electrical Installation
Chapter 3 Mechanical and Electrical Installation
Function level code: A -braking unit inside
B -non braking unit
Input voltage2-220V 4-400V 6-660V
Freq. RangeL0-600.0Hz
Applicable motor capacity0 01 51 . 5K W
SeriesB:General-Purpose Model
P:Fan&Pump Model
Seri es name: DZB300Serie s
3. 1 Mechanical Installation
1. Installation Environment
1) Ambient temperature: Ambient temperature influences the inverter life greatly, so it should be within
the range of -10~50.
2) Mount the inverter in a flame retardant s urface and the clearance around the inverter shall be enough
because the inverter will generate lots of heat during runni ng, besides mount the inverter on the base
vertically with screws.
3) Mount in the location where vibration is le ss than 0.6G; the inverter shall be far away from impact ing
lathe.
4) Please do not install the inverter in the place with direct sunlight, high humidit y and water.
5) Mount the inverter in the location free o f corrosive gas, explosive gas or combustible gas.
6) Mount the inverter in the location free of oi l dirt, dust, and metal powder.
2.Installation Location
up
1 0 0 m m
DZB
A
DZB
A
right
1 0 0 m m
DZB
Note: No need to consider the dimension
A for inverter of 22kW or below.
A shall be bigger than 50mm for the
inverter of 22kW or above
I ns ta ll at ion o f s i ng le i nv er te r
Note: Install an airflow- guidance
plate for the up and down installation
of inverters.
U p a nd d ow n i nst al la ti on o f i nv er te rs
Fig.3-1 DZB Series Inverter Installation Location
The user shall focus on the heat dissipation issues when installing the inverter, and pay attention to the
following points:
1) Install the inverter vertically so th at the heat may be expelled from the top, but do not install the
inverter upside down. When two Variable Speed Drives are mou nted up and dow n, an air flow
diverting plate should be fixed in between as shown in Fig. 3-1.
2) Installation space is shown in Fig.3-1 so as to ensur e the heat dissipation space, but consider the
heat dissipation of other components when placing the i nverter.
3) The installation bracket must be flame retardant.
4) Install the heat sink outside of the cabinet if the i nverter is installed in the area with metal powder.
And in this case, the space inside the sealing cabi net shall be big enough.