Traverse frequency function is suitable to industries such as textile, fiber and so on, and t o applications
which require traversing and winding functions.
Output frequency
5/14/2018 Traverse frequency function means that the inverter output frequency is traversing up an d down around Fuling Inverter User Manual - slidepdf.com
the set frequency. The operating frequency locus with time axis is shown as following diagram, in which
the amplitude of traverse is set by F4.07 . When F4.07 is set to be 0, i.e. traverse range is 0, the traverse
Setting frequency
frequency function will be inactive.
FDT delay
Operation Frequency
Upper TraverseFrequency
CenterFrequency
Kick Frequency
Lower TraverseFrequency
Accelerate on
Acceleration Time
Traverse Frequency
Fall Time
Traverse Frequency
Rising Time
Decelerate on
D e c e l e ra t i o n T i m e
Time t
Fig. 6-15 Traverse Frequency Operation Diagram
Traverse frequency range: traverse operation frequency limits by upper and lower limit frequency.
Traverse range relative to the center frequency: amplitude of traverseAW = CF × AW range F4.07
Kick frequency = amplitude of traverseAW × Kick Frequency Range F4.08. I.e. the kick frequency is
the value relative to amplitude of traverse at traverse-frequency operation.
Traverse frequency rising time: the time required to rise from the lowest traverse frequency to the
highest traverse frequency.
Traverse frequency fall time: the time required to fall from the highest traverse frequency to the lowest
traverse frequency.
Function
Code
Name
F4.11 Fault auto-reset times
F4.12
Interval time setting of
automatic resetting fault
0~3
Setting Range
0.1~100. 0s
Default
Value
0
1.0s
Fault auto-reset times: used to set the auto-reset tim es when inverter chooses fault auto-reset. If this
value is exceeded, inverter will wait for trouble shooting.
Interval time setting of fault auto-reset: chos e the interval time between fault occurring a nd automatic
resetting actuated
Function
Code
Name
F4.13 FDT level detection value
Setting Range
0 .0 0~ F 0. 04
F4.14 FDT delay detection value 0.0~100. 0%(FDT l ev el )
Default
Value
50.00Hz
5.0%
Set output frequency detection v alue and the delay value of output ac tion dismissed, as shown by
following figure:
Frequency detection
signal
Time t
Time t
Fig.6-16 FDT Level Diagram
Function
Code
Name
F4.15
Frequency reaching
detection range
Setting Range
0.0~100.0%(maximum frequency)
Default
Value
0.0%
When the inverter output frequenc y reaches the set frequency value, this funct ion can regulate its
detection range value, as shown by foll owing figure:
Output frequency
Setting frequency
Detection range(F4.15)
Frequency detection
signal
Time t
Time t
Fig.6-17 Frequency Reaching Detection Range Diagram