Function
Code
Name
F 5/14/2018 2.23 AO L ower li mi t
F2.24
Lower limit corresponding
AO output
F2.25 AO Upper limit
F2.26
Upper limit corresponding
AO output
Setting Range
0.0 %100.0 %
0 . 0 0V1 0 .0 0 V
0 .0 %1 0 0. 0 %
0 . 0 0V1 0 .0 0 V
Default
Value
0.0%
0.00V
100.0%
10.00V
Above function codes define the relationship betwee n output value and analog output
corresponding output value. When the output value exc eeds the maximum output or the
minimum output range, the beyond portion should be cal culated with maximum output or
minimum output.
When analog output is current output, 1mAis equivalent to 0.5V
For different applications, the analog ou tput corresponding to 100% output value is
different. For details, plea se refer to the instruction of each application.
Following figures explain several setting circumstances:
10V(20mA)
0
100% output
Figure 6-13 The coincidence relationship between assi gned value and analog output
F3 Human Machine Interface Parameters
Fuling Inve r te r Use r Ma nua l - slide pdf.c om
Function
Code
Name
F3.00 User password
Setting Range
06 55 35
Default
Value
0
User password is applied to prevent non-a uthorized person to look and modify parameter.Input a
nonzero five digit n umber as password, the n press DATA/ENT to confirm, if t here is no button opera tion
in one minute, password function beco mes effective.
After password becomes effective, customer can not access parameter list if password input is
incorrect. Please remember t he password. If it is not necessary to set password, ju st set 00000 to clear
password.
Function
Code
Name
F3.01 Reserved
F3.02 Reserved
Setting Range
Default
Value
Function
Code
Name
F3.03 STOP function option
Setting Range
0Keypad control valid
1Keypad and terminal control
valid
2Keypad and communication
control valid
3All control modes valid
Default
Value
0
This function code is to define the STOP stop function validity options.
-53-
DZB Series http://slide pdf.c om/re a de r/full/fuling-inve r te r-use r-ma nua l
Chapter 6 Parameter Description
DZB Series
-54-
Chapter 6 Parameter Description 30/54
    "