DZB100 Series
Parameter Settings
F1-72 Auto Reset / Restart Operation after Fault
F1-
72
Parameter Name Auto reset / restart operation after fault
Factory Setting 0
Settings 0~10
Reset / restart operation may be performed up to 10 times after a fault has occurred.
Setting this parameter to 0 disables the reset / restart operation after any fault has occurred.
If a protective shut-down operation (E009,E00A) occurs during operation, the auto
reset / restart function can be selected. (Refer to Fault Names in Ch. 7)
F1-73 F1-74 F1-75 Fault Records
F1-
73 74 75
Parameter Name Three most recent fault records
Factory Setting 0000
Settings 0000 No errors occurred (Fault records clear)
0001 E009 (Over-current)
0002 E00A (Over-voltage)
0003 E00E (Overheat)
0004 E008 (Overload)
0005 Manufacture used diagnostics
0006 E00D (External fault)
0007 E015 (CPU failure 1)
0008 E004 (Over-current during acceleration)
0009 E006 (Over-current during deceleration)
0010 E005 (Over-current during steady state operation)
0011 E001 (Low -voltage)
0012 E001 (Low -voltage)
0013 E00F (CPU failure 2)
0014 E016 (External baseblock)
0015 E013 (Over-torque)
0016 E011 (Start warning)
0017 E012(Shortage of input phase)
0018~0020 Manufacture used diagnostics
These parameters store records of the three most recent faults that have occurred.
If failures are got rid of ,set the parameter to 0000 to clear the fault records.
-59-
    "