DZB100 Series
Parameter Settings
F1-67 Displays The User-difined Frequency
Read Only
F1-68 F1-69 F1-70 Skip Frequencies Setting
F1-
68 69
Parameter Name Skip frequency 1, 2
Factory Setting 0.00
Unit 0.01 Hz
Settings 0.00 400.00Hz
This parameter determines the two skip frequencies, which in conjunction with F1-70 [Skip
Frequency Band] will cause the AC drive to skip operation at these frequency ranges.
(See graph below)
F1-
70
Parameter Name Skip frequency band
Factory Setting 0.01
Unit 0.01Hz
Settings 0.01 20.00Hz
This parameter determines the frequency band of a given [Skip frequency]. half of which is
above and the other half is below the [Skip frequency] setting. Setting this parameter to 0.01
to disable all skip frequencies. (See graph below)
Output frequency
F1-68
F1-69
Skip frequency
set point
Adjustable range
Commandfrequency
(F1-70)/2 Frequency to
(F1-70)/2 be jumped
-57-