DZB100 Series
Parameter Settings
F1-60 F1-61 F1-62 Over-torque Detection Setting
F1-
60
Parameter Name Over-torque detection mode select
Factory Setting 0000
Settings 0000 Over-torque detection not enabled
0001 Over-torque detection during constant speed operation,
operation halted after over-torque detection
0002 Over-torque detection during constant speed operation,
operation continues after over-torque detection
0003 Over-torque detection during operation,
operation halted after over-torque detection
0004 Over-torque detection during operation,
operation continues after over-torque detection
This parameter determines the AC drive operation after an over-torque is detected.
Over-torque detection is based on the following: When the output current exceeds the
over-torque detection level (F1-61, factory preset value = 150%) and the overtorque
detection time (F1-62, factory preset value = 0.1 second, fThe Multi-function PHC
output 1 and 2 may be set to indicate an over-torque condition. Refer to F1-45, 46.
The Multi-function Indication Output (F1- 57) may also be set to indicate an over-torque
condition.
F1-
61
Parameter Name Over-torque detection level
Factory Setting 150%
Unit 1%
Settings 30 200%
This parameter sets the over-torque detection level at 1% increments. The AC drive rated
current is regarded as 100%.
F1-
62
Parameter Name Over-torque detection time
Factory Setting 1.3sec
Unit 0.1sec
Settings 0.1 10.0sec
This parameter sets the over-torque detection time in units of 0.1 second.
-54-
    "