DZB100 Series
Parameter Settings
F1-
53
Parameter Name Motor no-load current
Factory Setting 40%
Unit 1%
Settings 0 99%
This parameter can be programmed while the drive is running.
This parameter sets the motor no-load current in 1% increments.
F1-54 Torque Compensation Setting
F1-
54
Parameter Name Auto torque-compensation
Factory Setting 0
Unit 1%
Settings 0 10%
This parameter can be programmed while the drive is running.
This parameter may be set so that the AC drive will increase the voltage output during
startup to obtain a higher initial starting torque. This additional torque will be present until
the master operating frequency is attained.
Be careful while setting the value for F1-54. If the value is too high, the motor might
overheat or be damaged.
F1-55 Slip Compensation
F1-
55
Parameter Name Slip compensation
Factory Setting 0.0
Unit 0.1
Settings 0.0 10.0
This parameter can be programmed while the drive is running.
This parameter is used to compensate for the nominal slip within a range of 0.0 -10.0.
When the output current of the AC drive is greater than the motor no-load current (F1-53),
the AC drive will adjust its output frequency according to F1-55.
F1-56 Reserved
-52-