DZB100 Series
Parameter Settings
F1-50 Analog Meter Output Select
F1-
50
Parameter Name Analog meter output select
Factory Setting 0000
Settings 0000 Analog frequency meter ( 0 to [Maximum Frequency])
0001 Analog current meter (0 to 250% of the rated drive output current)
This parameter selects the analog Meter output for either output frequency or output current
(refer to Control Terminals FM, ACM).
F1-51 Automatic Voltage Regulation (AVR) Setting
F1-
51
Parameter Name Automatic voltage regulation (AVR) select
Factory Setting 0001
Settings 0000 Disable automatic voltage regulation (AVR)
0001 Enable automatic voltage regulation (AVR)
This parameter determines whether the automatic voltage regulation function is enabled.
When input voltage output voltage pre-set
this function will ensure output voltage invariablenes.
When input voltage output voltage pre-set
this function will ensure Output Voltage Proportional to Input Voltage
F1-52 F1-53 Motor Current Setting
F1-
52
Parameter Name Motor rated current
Factory Setting 100%
Unit 1%
Settings 30 120%
This parameter can be programmed while the drive is running.
This parameter must be set according to the motor specification found on its nameplate.
This setting will limit the AC drive output current in order to prevent the motor from
overheating. When the motor current exceeds this value, the output frequency will be
reduced until the current drops below this limit.
-51-