DZB100 Series
Parameter Settings
Note: The absolute value of the difference between the settings of F1-48 and F1-49 should be
greater than or equal to 3.
F1-03
Output frequency
F1-03
Output frequency
F1-08
0V F1-49
F1-48 10V
Analog input signal level
F1-08
0V F1-48
F1-49 10V
Analog input signal level
The analog input signal level is the combined input signals from the analog voltage input
(VI) (0 - 10 V) and analog current input (CI) (4 - 20 mA). The voltage corresponding to
the analog current input (4 - 20 mA) and analog input signal level is defined as follows:
Voltage corresponding 10V
to the analog input
signal level
5V
0V
4mA
12mA 20mA
Analog current frequency command
An example of such application may be illustrated as follows:
Output frequency 60Hz
Output frequency 60Hz
F1-03 =60.00Hz
F1-08 =1.50Hz
F1-48 =5.0V
F1-49 =0V
1.50Hz
F1-03 =60.00Hz
F1-08 =1.50Hz
F1-48 =5.0V
F1-49 =1V
1.50Hz
0V
5V 10V
Analog input signal level
0V 1V 5V 10V
Analog input signal level
-50-