DZB100 Series
Parameter Settings
F1-47 Desired Frequency Attained Setting
F1-
47
Parameter Name Desired frequency attained setting
Factory Setting 0.00
Unit 0.01 Hz
Settings 0.00 400.00 Hz
Used to select a specified frequency, set in increments of 0.01 Hz. ( See F1-45, 46 )
F1-48 F1-49 Analog Input Setting for Output Frequency Range
F1-
48
Parameter Name Maximum output frequency voltage setting
Factory Setting 10.0
Unit 0.1V
Settings 0.0 10.0V
This parameter can be programmed while the drive is running.
Sets the input signal voltage level (0 ~ 10V) that corresponds to the maximum output
frequency (F1-03). Used in conjunction with F1-49, this parameter may be used to set the
analog input for frequency command curve setting.
F1-
49
Parameter Name Minimum output frequency voltage setting
Factory Setting 0.3
Unit 0.1V
Settings 0.0 10.0V
This parameter can be programmed while the drive is running.
Sets the input signal voltage level (0 ~ 10V) that corresponds to the minimum output
frequency (F1-08).
-49-