DZB100 Series
Parameter Settings
F1-38 External Control Terminal Configuration
F1-
38
Parameter Name 2-wire / 3-wire operation control selection
Factory Setting 0000
Settings 0000 FWD / STOP, REV / STOP
0001 FWD / REV, RUN / STOP
0002 3-WIRE operation control mode 1
0003 3-WIRE operation control mode 2
This parameter determines the control functions and operating modes available through the
external control terminals.
The following configurations are available:
F1-38
Control terminal wiring diagram
0000
Two wire
FWD / STOP
REV / STOP
FWD/STOP
REV/STOP
FWD"Open" : Stop; "Close" : FWD Run
REV "Open" : Stop; "Close" : REV Run
DCM
0001
Two wire
REV / FWD
RUN / STOP
RUN/STOP
REV/FWD
FWD"Open" : Stop; "Close" : Run
REV "Open" : FWD; "Close" : REV
DCM
0002
Three wire
operation control
mode 1
STOP
RUN
REV/FWD
FWD (Run command, Runs when "Close")
EF (Stop command, stops when "Open")
REV ( REV/FWD Run select
"Open" : FWD Run "Close" : REV Run)
DCM
0003
Three wire
operation control
mode 2
F WD
REV
STOP
FWD "Close" : FWD Run
REV "Close" : REV Run
EF (Stop command, stops when "Open")
DCM
-44-
    "