DZB100 Series
Parameter Settings
F1-
35
Parameter Name Speed search current limit
Factory Setting 150%
Unit 1%
Settings 30 200%
Following a power failure, the AC drive will start its speed search operation, only if the
output current is greater than the value determined by F1-35.When the output current is less
than that of F1-35, the AC drive output frequency is at a "speed synchronization point".
The drive will start to accelerate or decelerate back to the operating frequency at which it
was running prior to the power failure.
INPUT
POWER
Allowable maximum
power loss time
F1-33
OUTPUT
FREQUENCY
F1-32 =0001
Speed search starts with
the frequency reference value
Speed synchronization
detection
OUTPUT
VOLTAGE
INPUT
POWER
F1-34
Min. baseblock
time
Allowable maximum
power loss time
Speed search
operation
F1-33
OUTPUT
FREQUENCY
F1-32 =0002
Speed search starts with
minimum starting frequency
OUTPUT
VOLTAGE
F1-34
Min. baseblock time
-42-