DZB100 Series
Parameter Settings
F1-
29
Parameter Name DC braking time during start-up
Factory Setting 0.0
Unit 0.1sec
Settings 0.0 5.0sec
This parameter determines the time duration that DC braking voltage will be applied to the
motor during the AC drive start-up.
F1-
30
Parameter Name DC braking time during stopping
Factory Setting 0.0
Unit 0.1sec
Settings 0.0 25.0sec
This parameter determines the time duration that DC braking voltage will be applied to the
motor when the Motor Stop Method is set to "Ramp Stop".
F1-
31
Parameter Name DC braking starting frequency
Factory Setting 0.00
Unit 0.01Hz
Settings 0.00 60.00Hz
This parameter determines the frequency at which DC breaking will start during AC drive
deceleration. The frequency may be set in 0.01 Hz increments. When the preset value is less
than that specified by F1-08 (Minimum output frequency), the starting frequency for DC
braking will be the F1-08 frequency.
Minimum output
frequency
F1-08
DC brake starting frequency
F1-31
F1-29
DC braking voltage
F1-28
F1-30
-40-
    "