Parameter Settings
F1-24 REV Run Setting
F1-
24
Parameter Name REV Run
Factory Setting 0000
Settings 0000 REV run enabled
0001 REV run disabled
This parameter determines whether the AC Drive can operate in the reverse direction.
F1-25 Over-voltage Stall Prevention
F1-
25
Parameter Name Over-voltage stall prevention during deceleration
Factory Setting 0001
Settings 0000Disable over-voltage stall prevention
0001Enable over-voltage stall prevention
During deceleration, the motor DC bus voltage may exceed its maximum allowable value due
to motor regeneration. When F1-25 is enabled and an over-voltage is detected, the AC drive
will cease to decelerate and will then maintain a constant output frequency. The drive will only
resume deceleration when the DC bus voltage drops below the preset value.
DC bus
voltage
Over voltage
detection
level
Output
frequency
Time
Time
Over voltage stall prevention