DZB100 Series
Parameter Settings
F1-
12
Parameter Name Acceleration time 2
Factory Setting 10.0sec
Unit 0.1sec
Settings 0.1 999.9sec
This parameter can be programmed while the drive is running.
This parameter determines the time required for the AC drive to ramp from 0 Hz to the
Maximum operating frequency (F1-03). The rate is linear unless S Curve is "Enabled."
Acceleration time 1 is the default. A Multi-Function Input Terminal can be programmed to
select Acceleration time 1 or Acceleration time 2. See parameters F1-39, 40, 41and 42.
F1-
13
Parameter Name Deceleration time 1
Factory Setting 10.0sec
Unit 0.1sec
Settings 0.1 999.9sec
This parameter can be programmed while the drive is running.
This parameter determines the time for the AC drive to decelerate from the Maximum
operating frequency (F1-03) down to 0 Hz. The rate is linear unless S Curve is "Enabled."
Deceleration time 1 is the default. A Multi-Function Input Terminal can be programmed to
select Deceleration time 1 or Deceleration time 2.See parameters F1-39, 40,41 and 42.
F1-14 Jog Accel / Decel Time
F1-
14
Parameter Name Jog Accel / Decel time select
Factory Setting 10.0sec
Unit 0.1sec
Settings 0.1 600.0sec
This parameter can be programmed while the drive is running.
This parameter determines the time required for the AC Drive to ramp from 0 Hz to the Jog
frequency and the time required to ramp from the Jog frequency to 0 Hz.
-34-