DZB100 Series
Parameter Settings
F1-
07
Parameter Name Mid-point voltage
Factory Setting 20.0V
Unit 0.1V
Settings 2.0 250.0V for 220V Series. 2.0~400.0V for 400V Series.
This parameter sets the Mid-point voltage on the V/F curve. It may be used to determine the
V/F ratio between the Minimum frequency and the Mid-point frequency.
F1-
08
Parameter Name Minimum output frequency
Factory Setting 1.50Hz
Unit 0.01Hz
Settings 0.01 20.00Hz
This parameter sets the minimum output frequency of the AC Drive.
F1-
09
Parameter Name Minimum output voltage
Factory Setting 20.0V
Unit 0.1V
Settings 2.0 50.0V for 220V Series. 2.0~100.0V for 400V Series.
This parameter sets the minimum output voltage of the AC Drive.
Voltage
F1-05
Standard V/F Curve
F1-07
F1-09
0
F1-06
F1-08
F1-03
F1-04
Frequency
Voltage
F1-05
F1-07
F1-09
0
F1-08
Custom V/F Curve
Voltage
F1-05
F1-06 F1-04
F1-03
F1-07
F1-09
Frequency
F1-08
Fan/Pump V/F Curve
Frequency
F1-06 F1-04 F1-03
-31-
    "