DZB100 Series
Parameter Settings
F1-03 F1-04 F1-05 F1-06 F1-07 F1-08 F1-09 V/FCurve
F1-
03
Parameter Name Maximum output frequency
Factory Setting 60.00Hz
Unit 0.01Hz
Settings F1-04 400.00Hz
This parameter determines the AC drive's maximum output frequency. All the AC drive
analog inputs (0 - 10V, 4 - 20mA) are scaled to correspond to the output frequency range.
F1-
04
Parameter Name Maximum voltage frequency (Base frequency)
Factory Setting 50.00Hz
Unit 0.01Hz
Settings 10.00 F1-05
This value should be set according to rated frequency of the motor as indicated on the motor
nameplate.
F1-
05
Parameter Name Maximum output voltage
Factory Setting 220.0Vfor 220 V Series. 380.0Vfor 400 V Series.
Unit 0.1V
Settings 50.0 250.0Vfor 220 V Series. 50.0~400.0Vfor 400 V Series.
This parameter determines the Maximum Output Voltage of the AC drive. The maximum
output voltage setting must be smaller than or equal to the rated voltage of the motor as
indicated on the motor nameplate.
F1-
06
Parameter Name Mid-point frequency
Factory Setting 1.50Hz
Unit 0.01Hz
Settings F1-08~F1-04
This parameter sets the Mid-point frequency on the V/F curve. It may be used to determine
the V/F ratio between the Minimum frequency and the Mid-point frequency.
-30-
    "