DZB100 Series
Parameter Settings
Chapter 6 Parameter Settings
F1-00 Operating Frequency Source Select
F1-
00
Parameter Name Master Frequency source select
Factory Setting 0000
Settings 0000 Master Frequency determined by the digital keypad
0001 Master Frequency determined by the analog input signal
(0~+10V)+(4~20mA)
0002 Master Frequency determined by the RS-485 Interface.
This parameter is used to determine the AC drive command frequency source.
However, the actual AC drive command frequency may also be determined by [Jog
frequency], [Multi-step speed 1-7] or [Up / Down frequency], using the Multi-function
inputs 1, 2, 3,and 4. Refer to F1-39, 40, 41,42.
F1-01 Operation Command Source Select
F1-
01
Parameter Name Operation instructions source select
Factory Setting 0000
Settings 0000 Operating instructions determined by the digital keypad
0001 Operating instructions determined by the external terminal connections,
Keypad STOP key is enabled
0002 Operating instructions determined by the external terminal connections,
Keypad STOP key is not enabled
0003 Operating instructions determined by the RS-485 interface,
Keypad STOP key is enabled
0004 Operating instructions determined by the RS-485 interface,
Keypad STOP key is not enabled
This parameter is used to determine the source of the AC Drive operating instructions.
-28-
    "