DZB100 Series
Start Up
6. Operating frequency determined by remote control via the RS-485 serial interface;
RS-485 interface enabled to control AC Drive operation.
"Stop" key on digital keypad is enabled.(F1-00=0002 F1-01=0003)
1M
SG+ SG-
This completes the operation mode selection. Verify your operation mode works correctly,
then proceed to the next section for motor connection and initial operation.
4.2 Initial Operation - Setting Parameters and connecting the Motor.
Verify Minimum and Maximum Output Frequency Settings (F1- 08 and 03) arecorrect for your
application.
Verify the Motor Stop Method (F1-02) is correct for your application. If set to "Ramp to Stop",
then verify the Accel/Decel Time Settings (F1-10 and 11) are correct for your application.
Connect the motor to the terminals U, V, and W
Check for correct motor shaft rotation (counter clockwise when viewed from the shaft).
Verify the Stop command is functioning by pressing the Stop Key on the Digital Keypad or using
your Control Terminal Stop method.
This completes the basic start-up. Depending on the application, some parameter values may need
to be modified. Refer to Chapter 5 for parameter settings.