9MAINTENANCE AND CARE
As a result of ambient temperature, humidity, dust, vibration and aging of internal components of inverter,
the inverter will probably appear the potential problem during running. In order to ensure the inverter to run
steadily for a long time, the inverter should be checked up once at 3 to 6 months.
First of all, turn the inverter’s power off. And professional worker performs nance.
9.1 Daily Maintenance
The daily inspection and care can contribute to promptly discover different abnormal situations, find out the reasons for
abnormity, early eliminate hidden dangers of fault, ensure the equipment to normally run, and prolong the service life
of the converter. Please refer to the following table for the daily inspection and care
Inspection items
Running
Environment
Cooling
system
Inverter
Motor
Input/output
Parameters
Time
Daily Periodic
Inspection contents
1.Temperature,
Humidity
2.Dust, gase
1.Installation
Environment
2. Fan in inverter
1.Vibration,
Temperature raise
2. Noises
3. WireTerminal
1.Vibration,
Temperature raise
2. Noises
1. Input voltage
2. Output current
Criterion
1.When temperature is over 40, the panel should be
opened. Humidity is less than 90%, and no condensation
2. No peculiar smellno flammable and explosive gases.
1. Installation environment is well ventilated, and the duct is not
blocked.
2. Fan is normal and no abnormal voice.
1. Vibration smooth, the temperature of air outlet is normal.
2. Not abnormal voice and no peculiar smell
3. Fastening screw is not loosed.
1. Running smooth, and temperature is normal
1. Input-voltage is in the setup range
2. Output-current is under the rated value
Recommend the use of instrument
input voltage
Output voltage
O/I current
Moving-coil voltmeter
Rectifier-type voltmeter
Tong-type ammeter
Inverter has done the electric insulating experiment before leave-factory, so user don’t need to do the withstand
voltage test.
Do the insulation test to the inverter if necessary, all of I/O terminals must be connected in short-circuit
(R, S, T,L1,L2, U, V, W, P, P-, PB). Strictly prohibit from doing the insulation test for the single terminal. Please use
500V Meg-ohmmeter to perform this test.
Control circuit can not be used the Meg-ohmmeter to test.
For insulation test to motor, the connection wire between motor and inverter should be disassembled.
VS500 series of general purpose inverter Duxe.ru
    "