82 VICSION VS500
Parameter
Type
Code
Name
F0.17
Carrier wave
characteristics
F0.18
Parameter
write-protection
F1.0 Type of V/F Curve
F1.1 Torque Boost
F1.2 Torque boost pattern
Basic running
F1.3
frequency
F1.4 Max output voltage
F1.5
F1.6
F1.7
F1.8
F1.9
F1.10
F1.11
F1.12
F1.13 ~
F1.18
V/F freq. 3
V/F voltage 3
V/F freq. 3
V/F voltage 2
V/F freq. 1
V/F voltage 1
DC braking current
when starting
DC braking time
when starting
Reserved
Min.
Probable Causes
Unit
The first part of LED (form right to left):
Reserved
The second part of LED:
0:Load carrier wave adjustment is invalid
1:Load carrier wave adjustment is valid
The third part of LED:
0:Heat carrier wave adjustment is invalid
1
1:Heat carrier wave adjustment is valid
The fourth part of LED:
0:Freq. relating carrier wave adjustment is
Invalid
1:Freq. relating carrier wave adjustment is
valid
1:Forbid to modify all parameter, except
F0.2
and F0.18
2:Forbid to modify all parameter, except
1
F0.18
Other values: all parameters are allowed to
modify
0:Constant torque curve
1:Low-freq. torque curve 1
1
2:Low-freq. torque curve 2
3:V/F user-defined curve
0.0~20.0(%)
0.1
0:Manual 1:Automatic
1
5.00~the upper limit frequency
0.01
200~500V /100~250V
1
[F1.7]~[F1.3]
0.01
[F1.8]~100.0(%)
0.1
[F1.9]~[F1.5]
0.01
[F1.10]~[F1.6]
0.1
0.0~[F1.7]
0.01
[F1.1]~[F1.8]
0.1
0.0~100.0(%)
0.1
0.0~20.0Sec
0.1
Factory
Value
1110
0
3
▲
0
50.00
400
220
30.00
65.0
20.00
50.00
10.00
25.0
50.0
0
Modification
Limited
★
★
★
★
★
★
★
★
★
F2.0 ~ The same with the general definition of parameters, please refer to the general parameter table
F2.18