Duxe.ru VICSION VS500 79
7.3 Parameter table of drawing machine dedicated function ([F0.0] =0001)
The drawing machine dedicated parameter table can be used in comparison with the general parameter table, wherein,
the parameters in the shaded part are somewhat different from the parameters in the general parameter table (with
different value or definition), other parameters are identical with that defined in the general parameter table, and please
refer to the description of the general parameter table for the corresponding description and user guide.
Description of marks in the functional parameter table:
” means that the parameter cannot be changed during the running; “▲” means that the parameter is associated with
the inverter model.
Parameter
Type
Code
F0.0
F0.1
F0.2
F0.3
Name
Running mode
selection
Frequency input
channel / mode
selection
Frequency digital
setting
Auxiliary control of
freq. Digital setting
Min.
Probable Causes
Unit
LED bits : Running mode
0General mode
1Special for drawing machine
LED tens: Reserved
1
LED hundreds: Reserved
LED thousands: Reserved
0Frequency setting by operation panel
1UP/DW Acc and Dec control
2RS485 interface
3Panel potentiometer
4External voltage signal VC10V~5V
1
5External voltage signal VC20V~10V
6External current signal CC0~20mA
7External pulse signal0.0~50.0KHz
8Combination setting
9External terminals
0.00~ the upper limit frequency
0.01
The first part of LED(form right to left)
0Setting freq. will save after power down
1Setting freq. will not save after power
down
The second part of LED
0Setting freq. is to keep when stopping
1
1Setting freq. will save in F0.2 when
stopping
2Setting freq. is clear when stopping
The third and fourth part of LED(form right
to left)Reserved
Factory
Value
0001
2
0
0021
Modification
Limited
VS500 series of general purpose inverter Duxe.ru
    "