74 VICSION VS500
It defines measuring range of long-distance manometer, user have to input it.
F8.13 Sleeping threshold
Setting range[F8.14]~[F8.12]
It defines feedback value while inverter goes sleep state. When actual feedback value is larger than setting value and
inverter arrives lower limit value, the inverter will go sleep.
F8.14 Awakening threshold
Setting range::0.0~[F8.13]
It defines feedback value while inverter is in the state of sleeping. When actual feedback value is less than setting
value, the inverter will be in the sleepy state. The inverter will wait [F8.15] to switch modes, if the inverter receives
satisfied sleep or awakening condition. Shown as fig.6-31.
[F8.13]
PID setting
[F8.14]
output freq
Lower limit freq
[F0.7]
PID feedback value
Sleeping
threshold
Awakening
threshold
Sleeping
[F8.15]
Awakening
[F8.15]
Fig.6-31 Sleep and awakening function of PID
F8.15 Switching time of Sleeping/Awakening mode
Setting range::0.0~[F8.13]
When PID controller operates, switching time of sleeping/awakening mode is shown as fig.6-31.
F8.16 upper limit pressure value
F8.17 Lower limit pressure value
Setting range[F8.13]~[F8.12] Mpa
Setting range0.0 ~ 6000.0s
It is used for setting the upper and lower limit pressure value.
F8.18F8.24 Reserved
6.10 Communication function parameter units
F9.0 Communication setting
Setting range0000 ~ 0025
The first part of LED(form right to left)It is used for setting baud rate of serials communication.
0Reserved
11200bps
2: 2400bps
3: 4800bps
4: 9600bps
5: 19200bps
To make sure both sides have the same baud rate, when client use serials communication. The second part of LEDTo
set data format of serials communication.
0Close
1Even
2Odd
To make sure both sides have the same data format, when client use serials communication. The third and fourth part of
LED: Reserved
F9.1 Local address
Setting range0 ~ 30
F9.2 Response delay of local
Setting range0 ~ 1000 ms