Adjusted setting freq
Duxe.ru VICSION VS500 69
Skip freq 2
Skip freq 1
Amplitude
accumulation of
Skip freq. 2
Amplitude accumulation of
Skip freq. 1
Fig.6-26 Skip freq
F6.9 Linear speed coefficient setting
Setting range0.01 ~ 100.0
This parameter is used for confirming the display value of running linear speed and setting linear speed, and displaying
other value being positive ratio with the output frequency.
Running linear velocityd.10= [F6.9] × output frequency (d.0)
Setting linear velocityd.11= [F6.9] × Setting frequency (d.6)
F6.10 close-loop analog coefficient setting
Setting range0.01 ~ 100.0
PID feedback valued.9= [F6.10] × actual feedback value
PID setting valued.8= [F6.10] × setting value
F6.11 rotator speed coefficient setting
Setting range0.01 ~ 10.00
It is used for rectifying the display value of rotator speed.
rotator speedd.3= [F6.11] × actual output rotator speed
F6.12 Monitor item selection 1 / Main display
F6.13 Monitor item selection 2 / Auxiliary display
Setting range0 ~ 11
Setting range0 ~ 19
This parameter is used for confirming display content of operation panel in state monitor mode.
F6.14 Query or modify parameters
It is used for getting check code to query or modify parameters.
Setting range : 0 ~ 9999
F6.15 parameter initialization
Setting range0 ~ 3
It is used for modifying inverter’s parameters to manufacture setting.
0Parameter initialization is off.
1Parameter initialization is on.
Parameter F0F9 return to manufacture setting. The following parameters can’t be initialized
VS500 series of general purpose inverter Duxe.ru
    "