68 VICSION VS500
6.7 Advanced running parameter unit
F6.0 interna timer
Setting range:0.1 ~ 6000.0 Sec
It is used for setting the internal timer. The internal timer is triggering start-upped by external terminals X1~
X6, external terminals X1~X6 should be set as 24(explained by parameters F3.0~F3.5).
Internal timer arrives the regular time, OC1、OC2 or TA,TB,TC will output 0.5s width pulse (set by F3.6~
F3.8)
The function can realize the timing operation shutdown.
F6.1 Fault self-recovery time
F6.2 Interval time of fault self-recovery
Setting range:0 ~ 2
Setting range:0.2 ~ 20.0s
F6.1 is used for resetting some faults and run again
F6.2 defines interval time between fault starting and fault recovery. If inverter can’t recover in setting value
of F6.1, it will output fault signal. Inverter will check speed and restart.
Inverter can’t self-recovery about overheat or overload protect
F6.3 Final value setup of internal counter
F6.4 Internal timer setup
Setting range:1 ~ 60000
Setting range:1 ~ 60000
The parameter defines the counting action of internal counter, and the clock terminals of counter are selected by
parameter F1.6.
The counting value of counter for the external clock reaches the value appointed by parameter F3.5, and the
corresponding Terminal OC outputs a valid signal of same width with the external clock cycle.
When the counting value of counter for external clock reached the value appointed by Parameter F6.3, the
corresponding Terminal OC will output the valid signal, Go on counting to the value provided by parameter F6.4,
which will lead to reset and the output valid signal will be withdrawn.
The clock cycle of counter should be over 5ms and the min width should be 2ms
[F6.3]
[F6.4]
Pluse
OC
OC
Fig.6-25 Internal counter function
F6.5
F6.6
F6.7
F6.8
Skip freq. 1
Amplitude accumulation of Skip freq. 1
Skip freq.2
Amplitude accumulation of Skip freq.
Setting range:0.0 ~ upper frequency
Setting range:0.0 ~ 5.00Hz
Setting range:0.0 ~ upper frequency
Setting range:0.0 ~ 5.00Hz
It is used for avoiding resonance point of mechanical load. Shown as fig. 6-26