2Restart from setting freq. when the running is breaking.
When inverter stop, caused by fault or receiving stop instrument in PLC running, setting of running time and freq. of a
certain stage will be saved. And inverter will restart form setting of running time and freq. the different between mode
1 and mode 2 is initial freq. Shown as fig6-24.
The fourth part of LEDPLC save state
0Non-save after power off
It will not be saved PLC running state after power off. Inverter will run form the stage 1 when power is on.
1Save after power off
It will save PLC running state after power off. Inverter will run form the stage 1 when power is on
f
[F5.3]
[F5.8]
[F5.2]
[F5.1]
[F5.20] [F5.21]
[F5.6]
[F5.5]
[F5.16] [F5.17] [F5.18]
t
[F5.23]
f
[F5.3]
[F5.8]
[F5.1]
[F5.16]
[F5.18]
stop
[F5.23]
Mode1
t
Instruction
Each stage
Whole Cyc
OC output
OC output
Fig.6-24 a PLC recover running after restart
[F5.3]
[F5.8]
[F5.1]
stop
Mode2
t
[F5.16 [F5.18]
[F5.23]
Fig.6-24 b PLC recover running after restart
[F5.1][F5.15] Multi-speed freq.115
Those parameters are used for setting output freq. of multi-speed.
[F5.16][F5.23] Running time of Multi-speed 1~8
Those parameters are used for confirming running time of each stage.
F5.24][F5.25] Running direction of PLC multi-speed
Those parameters are used for defining running direction of PLC multi-speed
[F5. 24]
The first part of LED(form right to left)
0Stage 1 FWD
1Stage 1 REV The second part of LED
0Stage 2 FWD
1Stage 2 REV The third part of LED
0Stage 3 FWD
1Stage 3 REV The fourth part of LED
0Stage 4 FWD
1Stage 4 REV [F5. 25]
The first part of LED(form right to left)
0Stage 5 FWD
1Stage 5 REV The second part of LED
0Stage 6 FWD
1Stage 6 REV The third part of LED
0Stage 7 FWD
1Stage 7 REV The fourth part of LED
0Stage 8 FWD
1Stage 8 REV
F5.26 PLC timing running shutdown
Setting range00009999min
When PLC multi-speed running function is valid, it is used for setting PLC multi-speed running, beyond the time, it
will automatically shutdown. To recovery operations, first give a shutdown instruction, and then give a start-up
instruction. When the parameter equals 0, timing running shutdown function is invalid.