F4.26 Restart after power down setting
F4.27 waiting time of restart after power down
Setting range0000 ~ 0011
Setting range0.0 ~ 10.0s
Parameter F4.26
The first part of LED
0Invalid 1Valid
When restart after power down setting is invalid, the inverter will clear automatically all running command
and run according to new command after power on.
When restart after power down setting is valid, the inverter will save all running command and run according
to the save command after power on.
Please make sure that other equipments in system are ready before using function of restart after power
Down.
The second part of LED
Applied motor is still running when user select restart. Here, users have to select function of checking speed
and restarting.
The third and fourth part of LED: reserved.
F4.28 REV jog frequency
Setting range0.0 ~ Upper limit
6.6 Multi-speed running parameter unit
F5.0 Multi-speed running mode
F5.1 Multi-speed frequency 1
F5.2 Multi-speed frequency 2
F5.3 Multi-speed frequency 3
F5.4 Multi-speed frequency4
F5.5 Multi-speed frequency 5
F5.6 Multi-speed frequency 6
F5.7 Multi-speed frequency 7
F5.8 Multi-speed frequency8
F5.9 Multi-speed frequency 9
F5.10 Multi-speed frequency 10
F5.11 Multi-speed frequency 11
F5.12 Multi-speed frequency12
F5.13 Multi-speed frequency 13
F5.14 Multi-speed frequency 14
F5.15 Multi-speed frequency 15
F5.16
F5.17
F5.18
F5.19
F5.20
F5.21
F5.22
F5.23
Running time of Multi-speed1
Running time of Multi-speed2
Running time of Multi-speed3
Running time of Multi-speed4
Running time of Multi-speed5
Running time of Multi-speed6
Running time of Multi-speed7
Running time of Multi-speed8
Setting range0000 ~ 1252
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ the upper limit freq
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s
Setting range0.0 ~ 6000s