60 VICSION VS500
If output freq. of inverter is within setting value that is set by F3.9, selected terminal will output valid signal. Shown
as fig.6-15
F3.10
F3.11
F3.12
F3.13
FDT setting 1
FDT output delay time 1
FDT setting 2
FDT output delay time 2
Setting range:0.0 ~ upper limit freq.
Setting range:0.0 ~ 200.0 s
Setting range:0.0 ~ Setting range
Setting range:0.0 ~ 200.0 s
The parameter is used for setting the frequency detection level. When output frequency is higher than the setting
value of FDT, after the setting delay time, terminals will output the valid signal, shown as fig.6-15. Parameters F3.10
and F3.11 are used for setting FDT of OC1, parameters F3.12 and F3.13 are used for setting FDT of OC2
F3.14 Overload alarm level
F3.15 Overload alarm delay time
Setting range:50 ~ 200(%)
Setting range:0.0 ~ 20.0s
If output freq. beyond the setting value set by parameter F3.14, after the setting delay time set by parameter
F3.15, terminals output valid signal, shown as fig.6-16
F3.16 Reserved
6.5 Auxiliary running parameter unit
F4.0
F4.1
F4.2
Start mode
Start frequency
Start frequency duration
Setting range:0~1
Setting range:0.0~10.00Hz
Setting range:0.0~20.0s
Those parameters are used for defining characteristic with relation to start mode, shown as fig6-17. The
explanation of F4.0 is shown as follows.
0: Routine mode
It is fit for mostly load, which have not special demand.
1:Detect speed and restart
It is fit for fault reset and restart occasion, or, power off and restart occasion. Inverter will judge automatically running
speed and direction of motor. Motor, which have not stop, will start up directly according to detect result.
Start frequency:It is fit for system, which are big inertia, heavy load and high start torque
f
S etting
freq
[F 4 .1 ]
[F4 .2 ]
Start
D ec e lerate s top
w ith no D C braking
Free stopt
t
F4.3 Stop mode
Fig6-17 Start and stop freq output curve
Setting range:0 ~ 1
0: Decelerate mode
Inverter will gradually decrease output freq. to 0 according to Dec time when stopping.
1: Uncontrolled stop
VS500 series of general purpose inverter Duxe.ru