0: Control terminal is idle
1: Multi-speed control terminal 1
2: Multi-speed control terminal 2
3: Multi-speed control terminal 3
26: Multi-speed control terminal 4
Combination of multi-speed control terminals is used for selecting output freq. of multi-speed.
4: Wobble freq. is valid
When F7.0 is ###2 and any of those parameters is set 4, wobble freq. is valid.
5: State of wobble freq. reset
When inverter is stop and F7.0 is ##0#, forcible reset will work by setting those parameters.
6: FWD jog control
7: REV jog control
When F0.4 is ###1 and any of those parameters is set 6 or 7, external jog signal is valid.
8: Acc& Dec time selection terminal 1
9: Acc& Dec time selection terminal 2
They are used for selecting external terminals Acc/Dec time 1~4.
10: Freq. setting channel selection 1
11: Freq. setting channel selection 2
12: Freq. setting channel selection 3
When F0.1 is 9, Frequency input channel is set by terminals state of 10, 11 and 12. See the explanation about
parameter F0.1.
13:Freq. is controlled gradually increase (UP)
14: Freq. is controlled gradually decrease (DW)
15: UP-DW freq. clear
When F0.3 is##0#, one of terminal X1~X6 defined by this parameter has function of forcible clear.
16: Uncontrolled stop control
If one of terminal X1~X6 defined by this parameter is connected with CM, the inverter will lock output signal and
applied motor will uncontrolled stop. Then inverter will detect speed and restart after terminal is disconnected with
CM.
17: Fault signal of peripheral equipment input
When one of terminal X1~X6 is defined by this parameter is connected with CM, peripheral equipment is fault. The
inverter will lock output signal and display FU.16.
18: Three-line mode running control
When F0.5 is 2, one of external terminal X1~X6 defined by this parameter is stop trigger switch of inverter. See
explanation about F0.5.
19: DC braking control
When inverter stops and one of external terminals X1~X6 defined by this parameter is connected with CM and output
freq. is lower than Initial freq. of DC braking, function of DC braking is valid until terminal is disconnected with CM.
Refer to explanation about F4.4~F4.7.
20: Inner counter clear
21: Inner counter timer
Only terminal X6 is used for Inner timer, namely parameter F3.5 is 21.
22: PLC running valid
When F5.0 is ###2 and any of those parameters is set 22, PLC running is valid.
23: PID running valid
When F8.0 is ###2 and any of those parameters is set 23, PID running is valid.。
24: Internal timer trigger terminal
The terminals is defined to be the internal timer trigger terminal
25: PLC state reset after stopping
VS500 series of general purpose inverter Duxe.ru