Duxe.ru VICSION VS500 53
They are nameplate parameters of applied motor. The running performance will improve if those parameters are input
correctly
F1.17 Droop control mode
Setting range01
Droop control is a special control mode that is used for poising output power when multi-inverters inverter the same
load. Output power will decrease automatically when output torque or current of a certain inverter is heavier than usual.
Some load will off, so the power will be poised.
The adjustment range of frequency changed with the load will decide by parameters FC.14, FC.15 and
FC.16.
0: Absolute droop
Actual output torque levelinitial level of droop
Actual output freq. of inverter =
Ending level of droopInitial level of droop
×Base running frequency [F1.3]
The max of actual freq. of inverter is setting freq..
When setting freq. of inverter is lower than base-running freq., ending level of inverter will reduce to 0 before inverter
run to ending level of droop
1Relative droop
Actual output freq. of inverte=
Actual output torque levelinitial level of droop
Ending level of droopInitial level of droop
×Setting frequency
The max of actual freq. of inverter is setting freq..
If output torque is beyond initial level of droop, output freq. will decrease. When output torque arrives ending level of
droop, actual output freq. will reduce to 0
F1.18 Reserved
6.3 Analog I/O parameter unit
F2.0 VC1 input lower limit voltage
F2.1 VC1 input upper limit voltage
Setting range0 .0 V ~ [F2.1]
Setting range[F2.0] ~ 5.0 V
F2.2 VC2 input lower limit voltage
F2.3 VC2 input upper limit voltage
F2.2 VC2 input lower limit voltage
F2.3 VC2 input upper limit voltage
Setting range0V ~ [F2.3]
Setting range[F2.2] ~ 10.0V
Setting range0V ~ [F2.3]
Setting range[F2.2] ~ 10.0V
F2.4 CC input lower limit voltage
F2.5 CC input upper limit voltage
Setting range0.0 mA ~ [F2.5]
Setting range[F2.4] ~ 20.0 mA
F2.6 the min pulse input
F2.7 the max pulse input
Setting range0.0 KHz ~ [F2.7]
Setting range[F2.6] ~ 50.0 KHz
[F2.0] and [F2.1] define the range of analog input voltage channel VC1, and it should be set according to the actual
input signal.
[F2.2] and [F2.3] define the range of analog input voltage channel VC2, and it should be set according to the actual
input signal.
VS500 series of general purpose inverter Duxe.ru
    "