Duxe.ru VICSION VS500 51
Auto torque boost can prevent the magnetic saturation, as the boost voltage is too high with light load, which can avoid
the over-heat phenomenon of motor in low frequency running.
F1.3 Base running frequency
F1.4 Max output voltage
Setting range: 5.00 ~ the upper frequency
Setting range: 200 ~ 500V/100~250V
Basic running frequency is corresponding to minimum frequency when output voltage of inverter is the highest.
Usually, it is rated frequency of motor.
Max output voltage is corresponding to output voltage when inverter outputs the basic running frequency.
Usually, it is rated voltage of motor.
F1.5 V/F freq. 3
F1.6 V/F voltage 3
F1.7 V/F freq. 2
F1.8 V/F voltage 2
F1.9 V/F freq. 1
F1.10 V/F voltage 1
Setting range: F1.7] ~ [F1.3]
Setting range:[F1.8] ~ 100%
Setting range: [F1.9] ~ [F1.5]
Setting range:[F1.10] ~ [F1.6]
Setting range:0.0 ~ [F1.7]
Setting range:[F1.1] ~ [F1.8]
Those parameters are used for setting user-defined curve which user need. Shown as Fig.6-6 below:
Voltage
[F1.4]
[F1.6]
[F1.8]
[F1.10]
[F1.1]
[F1.9]
[F1.7] [F1.5] [F1.3]
Fig.6-6 V/Fuser-defined curve
F1.11 DC braking current when starting
F1.12 DC braking time when starting
Freq
Setting range:0.0 ~ 100.0(%)
Setting range:0.0 ~ 20.0 S
This functional parameter is used for occasion that the inverter needs braking before starting, and please refer to Fig.
6-7. [F1.11] defines the percentage of DC braking against the rated current of inverter during start of inverter
When rated current of motor is lower than rated current of inverter, please pay attention to set,F1.11.Make sure that
DC braking current is lower than rated current of motor
Parameter F1.12 defines duration that inverter output DC braking current. When F1.12 is 0, DC braking is
invalid when starting.
VS500 series of general purpose inverter Duxe.ru