Duxe.ru VICSION VS500 15
Model
Applied MotorKW
G-load
P-load
Wire spec
(Main circuit)
mm2
Air-break
A
Magnetic
contactor
A
VS500-4T0450
45
55
50
200
115
VS500-4T0550
55
75
50
200
150
VS500-4T0750
75
90
70
250
170
VS500-4T0900
90
110
70
315
225
VS500-4T1100
110
132
95
400
225
VS500-4T1320
132
160
95
400
330
VS500-4T1600
160
185
150
630
330
VS500-4T1850
185
200
150
630
400
VS500-4T2000
200
220
185
630
400
VS500-4T2200
220
250
185
800
500
VS500-4T2500
250
280
240
800
500
VS500-4T2800
280
315
240
1000
630
VS500-4T3150
315
350
300
1250
630
Note: When inverters of same model of VS500 series are connected with loads from fan or water pump, the adaptive
motor power can be increased one power level as compared to connection with the generic loads.
3.3 Basic wiring
Three-phase Breaker
Three-phase
Power supply
×
R
×
S
×
T
X1
X2
X3
PLC input terminal
X4
X5
X6
CM
E
FWD Order
REV Order
Fault Reset
0 ~ 5V Frequency set
0 ~ 20mA Frequency set
0 ~ 10V Frequency set
0 ~ 50KHz Frequency set
FWD
REV
RST
CM
E
VS
VC1
CC
VC2
PLS
GND
E
Motor
U
V
M
W
E
Earth
Ta
Tb Fault alarm
Tc
P
P-
PB
External brake resistor
24V Auxiliary DC power
CM
AO1
AO2
GND
Voltmeter0~10V/ Current meter(0~20mA)
Voltmeter0~10V/ Current meter(0~20mA)
E
Open-circuit
Collector output
OC1
OC2
CM
E
VS500 series of general purpose inverter Duxe.ru
    "