Functional Details 67
LED Tens: Data format selection
0: No check
1: Even check
2: Odd check
When serial port communication is adopted, the communication parties must
have the same baud rate.
LED Hundreds: Protocol selection
0: RS485 protocol
1: MODBUS communication protocol
LED Kilobit: Reserve
F4.01 Local address
Setting range: 0 ~ 30
The local address set for communication of this inverter is only effective when
this inverter is used as the slave machine. During communication, this inverter
only sends back response frame for data frames corresponding to the local
address, and receives command.
With the SIMPHOENIX self-defined protocol, the address 31 is the broadcasting
address, and 0 represents the broadcasting address in the case of MODBUS
communication. For broadcasting data, the slave machine executes command
but does not give feedback of corresponding data (see the appendix of
communication protocol).
F4.02 Local response delay
Setting range: 0 ~ 1000 ms
The waiting time till sending response data frame after the local inverter has
correctly received information code of the upper computer.
F4.03 Setting of communication auxiliary function Setting range: 0000 ~ 0011
LED UNITS: Main and slave inverter setting
0: This inverter is the main inverter
1: This inverter is a slave inverter
When multiple inverters requires linkage synchronous control, one of inverters
should be set as the main inverter.