64 Function Parameter Table
F3.22 PLC multi-stage running direction Setting range: 0000 ~1111H
Define PLC multi-speed running direction (fratile binary system setting)
LED UNITS: Stage 1 direction selection
0: FEW
1: REV
LED Tens: Stage 2 direction selection
0: FEW
1: REV
LED Hundreds: Stage 3 direction selection
0: FEW
1: REV
LED Kilobit: Stage 4 direction selection
0: FEW
1: REV
F3.23 PLC running timer
Setting range: 0 ~9999Min
When programmable multi-speed running function is selected, this parameter
can be used to set programmable multi-speed running time. When the set time is
reached, it will automatically stop. For restoring running, it is required to input
stop command before the start command.
When this parameter is set to 0, timed running stop is void.
F3.24 Fault self-recovery times
Setting range: 0~5
F3.25 Fault self-recovery time
Setting range: 0.0~60.0Sec
During running of the inverter, load fluctuation, grid fluctuation and other
accidental factors may cause accidental shutdown of the inverter. At this time, in
order to ensure system’s working continuity, the inverter can be allowed to make
automatic resetting for some kinds of faults and restore running.
The self-recovery interval means the interval from the fault start to the
self-recovery. If the inverter cannot restore to normal condition within the set
self-recovery times, it will output fault signal. After successful self-recovery, the
inverter is at stop and ready status.
E500 Series Universal Low-Power Inverter
    "