Inverter Installation 5
2 Inverter Installation
2.1 Environmental requirements
This series of inverters are wall-mounted products and shall be vertically installed
to facilitate air circulation and heat dissipation. Following attentions shall be paid
for selecting installation environments.
1. The ambient temperature shall be within -10℃-40℃.
High-temperature and humid places shall be avoided, and the inverter
shall be better placed in a place with humidity lower than 90% and
without frosting.
2. Direct sunshine should be avoided.
3. The inverter should be away from flammable, explosive and corrosive
gas and liquid.
4. The environment should be free of dust, floating fibers and metal
particles.
5. The installation surface should be solid without ventilation.
6. The inverter should be away from electromagnetic
interference sources.
7. Please install the cover board of cooling holes if there is too much
powder in the using environment. (Refer to Fig 2-1-A).
cover board of cooling holes
Fig 2-1-A
Installation for cover board of cooling holes
If you have any special installation requirements, please contact us in advance.
See Figure 2-1-Bfor installation spacing and distance requirement for single
inverter. Enough space should be leaved around the inverter. For installation of
multiple inverters, baffle plate should be applied between inverters to ensure
good heat dissipation, as shown in Figure 2-1-C.
E500 Series Universal Low-Power Inverter