Chapter 5 Parameters
First numerator of electronic gear
P029
for command pulse
Range
1~32767
Default
value
1
Unit Usage
P
z Use the frequency division or multiplication for the input pulse and can conveniently match with each kind
of pulse source, also can achieve the pulse resolution for the user needs.
z The electronic gear numerator N of command pulse is determined by GEAR1 and GEAR2 from DI inputs.
The denominator M is set by parameter P030.
DI Signals [note] Numerator of electronic gear for command
GEAR2 GEAR1
pulse N
0
0
First numerator (parameter P029)
0
1
Second numerator (parameter P031)
1
0
Third numerator (parameter P032)
1
1
Fourth numerator (parameter P033)
Note: 0 indicates OFF; 1 indicates ON.
z The input pulse command becomes the position command by the N/M factor. The ratio range is:
1/50<N/M<200
f 2 = f 1× N
M
Denominator of electronic gear for
P030
command pulse
Range
1~32767
Default
value
1
Unit Usage
P
z This is electronic gear denominator M of command pulse. The application method refers to parameter P029.
Second numerator of electronic
P031
gear for command pulse
z Refer to the explanation of parameter P029.
Range
1~32767
Default
value
1
Unit Usage
P
62