Chapter 4 Running
3. Input mode of command pulse
The command pulse input mode is dependent on the parameter P035. For adjusting the counting edge of a
pulse, the parameter P037 sets the phases of the PULS and the SIGN signals. Parameter P036 uses in changing the
counting direction.
Note: The arrow indicates the counting edge with P306=0 and P307=0.
4. Timing chart specifications of command pulse
Pulse waveform of position command
Parameter demand
Differential Single end
tck>2μs
th>1μs
tl>1μs
trh<0.2μs
trl<0.2μs
ts>1μs
tqck>8μs
tqh>4μs
tql>4μs
tqrh<0.2μs
tqrl<0.2μs
tqs>1μs
tck>5μs
th>>2.5μs
tl>>2.5μs
trh<0.3μs
trl<0.3μs
ts>2.5μs
tqck>10μs
tqh>5μs
tql>5μs
tqrh<0.3μs
tqrl<0.3μs
tqs>2.5μs
38