Parameter Modification Mode (PA--)
Press Ente to enter the parameter modification mode PA--. Press and to increase or decrease a
parameter number. Press Enter to enter and modify a parameter. The decimal points at the lower right corner of
the digital tube will lighten when a parameter is being modified; and they will go out when Enter is pressed
again. Press to return.
PA--0 --Parameter password 385 -- User password
PA--1 - Motor type code
-
51 --Stands for 15015 type motor
PA--4 --Control mode selection 0 --Position control mode
Table 5.3 Operation of Parameter Modification Mode
Parameter Management Mode (EE--)
Press Enter to enter the parameter management mode EE-- . Press and to increase or decrease a
parameter. Finding a menu that should be stored or restored and pressing Enter for more than 3 seconds will
make Finishdisplay, which means that the operation is successful and will be effective after power cut
off. Error--will appear in case of failure or incorrect password.
EE--SET -- Store parameter Enter –Press down for more than 3 seconds
EE--RD -- Read parameter Enter –Press down for more than 3 seconds
EE—BA -- Backup parameter Enter –Press down for more than 3 seconds
EE—RS -- Restore backup Enter –Press down for more than 3 seconds
EE--DEF –Restore default Enter – Press down for more than 3 seconds
Table 5.4 Operation of Parameter Management Mode
1. EE—SET write in parameter. The password for Parameter PA—0 should be 315. EE—SET is mainly used to
store a parameter permanently.
2. EE—BD backup parameter means writing parameters with better effect in current servo state in the EEPROM
backup area and EE—RS is used in combination of EE—BD.
3. EE—BD restore backup means restoring the backup parameters in the backup area from EEPROM into a
parameter table.
4. EE—BD restore default is used to restore a default in case of parameter confusion or unclear reasons, etc.
when the new adaptive motor is debugged.
When restoring a default, find the corresponding motor model, set the password for PA—0 to 385 and PA--1 to the
type code corresponding to the motor, and then restore the default.
JOG Operational Mode (Jr- -)
Press Enter to enter the jog operation mode Jr--. Press Enter to enter jog operation mode ―J--. The jog speed
is set via Parameter PA21.
51
    "