Service Support Spirit
When the cutting torch touches the up limit or
the up limit is valid, the parameter setting is
11
E10
Upper limit alarm wrong, and the L06 parameter 1 or 0 is
reversed. After the upper limit switch returns to
normal, the alarm will disappear.
When the cutting torch touches the down limit
or the down limit is valid, the parameter setting
12
E11
Lower limit alarm is wrong, and the L06 parameter 1 or 0 is
reversed. After the upper limit switch returns to
normal, the alarm will disappear.
It will only appear in the capacitance height
adjustment mode. Check whether the
Disconnection
13
E12
connection between the capacitance sensor
alarm
cable of the capacitance height controller and
the system is loose.
It will only appear in the capacitance height
14
E13
Out of board alarm
adjustment mode.
This alarm will appear when the protective cap
collision signal continues to be sent for more
Protective cap
15
E14
than 3 seconds. If this alarm occurs, please
adhesion alarm
check whether the protective cap is out of order
and why the collision signal keeps emitting.
This alarm will appear when the proximity
switch collision signal continues to be sent for
Proximity switch more than 3 seconds. If this alarm occurs,
16
E15
adhesion alarm
please check whether the proximity switch is
malfunctioning and why the collision signal
keeps emitting.