Fault Diagnosis And Countermeasures 68
Monitoring
project
content
d-26
The fourth fault record
The output frequency of
d-27
the last fault recently
Monitoring
project
content
The module temperature of
d-31
the last fault recently
The fault information and condition monitoring parameters are stored in a unified
manner; please refer to the keyboard operation method to query information.
7.3 Fault reset
¾ The fault causes must be identified and removed completely prior
to reset, otherwise it may cause permanent damage to the inverter.
¾ If the inverter can’t be reset or fault occurs after reset, it’s necess-
ary to find out causes, otherwise continuous reset will damage the
inverter.
¾ The protection actions of overload and overheat should be delayed
for 5 minutes when reset.
To recover to the normal operation when the inverter fault occurs, it’s optional to
choose any of the following operations.
Method I: Press
RUN
STOP
key when displaying fault code.
Method II: Disconnect after closure of external multi-function terminals X1~X4
(fault reset) and CM.
Method III: Send the fault reset command via RS485 interface.
Method IV: Cut off power supply.
E550 Series Universal Low-Power Inverter
    "