Functional Details 47
F1.18 FDT (frequency level) setting
F1.19 FDT output delay time
Setting range: 0.0 ~ 1000 Hz
Setting range: 0.0 ~ 5.0Sec
This parameter group is used to set frequency detection level.
When the output frequency is higher than the FDT set value, after the set delay
time, the output terminal outputs effective signals.
When the output frequency is lower than the FDT set value, after the same delay
time, the output terminal outputs void signals.
F1.20 Overload alarm level
F1.21 Overload alarm delay time
Setting range: 50 ~ 200%
Setting range: 0.0 ~ 60.0Sec
This parameter is used to set the overload alarm level and alarm delay time. When
the output current is higher than the set value of [F1.20], afte the delay time set by
[F1.21], the output terminal outputs effective signals (low level). Refer to figure
6-10.
F1.22
F1.23
Reserve
Reserve
F1.24 Batter number of terminal machine
Setting range: 1~100
F1.25 Specified count value
F1.26 Initial count value
Setting range: 1~[F1.26]
Setting range: [F1.25]~60000
F1.27 Reserve
F1.28 Frequency input channel combination Setting range: 0~10
This parameter is only effective when the frequency input channel is set to
combined setting.
The inverter’s set frequency is determined by the liner combination of multiple