Functional Details 43
0: positive characteristic
1: negative characteristic
LED Kilobits: Define characteristics of X4 input channel
0: positive characteristic
1: negative characteristic
The positive characteristic is effective when the terminal is engaged and void when
the terminal is disconnected. The negative characteristic is effective when the term-
inal is disconnected and void when the terminal is engaged.
F1.13
F1.14
Output terminal OC function selection
Relay output TA/TC function selection
Setting range: 0 ~ 15
Setting range: 0 ~ 15
It is used to define the contents indicated by the collector open-circuit output termi-
nal OC and relay output contact. See Figure 6-8 for the internal wiring diagram of
the collector open-circuit output terminal. When the function is set to be effective,
the output is at low level, and when the function is void, the output is at the high-
resistance status.
Relay contact output: when the output function is set to be effective, the normally
open contact TA-TC is connected.
D
R
1
2
Figure 6-8 internal circuit of OC output terminal
For connecting external inductive elements (e.g. relay coil),
freewheel diode D must to be connected in parallel.
0: Inverter is running
When the inverter is running, it outputs effective signals, and when the inverter is
at stop, it outputs void signals.
E550 Series Universal Low-Power Inverter