Inverter Wiring 11
It can conveniently control power-supply and power disconnection of the
inverter, and the power-on and power-off of the motor.
AC reactor
1) To promote power factor;
2) To reduce harmonic input of the inverter against the grid;
3) Weaken influenced caused by unbalanced voltage of three-phase power
supply.
Brake resistance
When the motor is at the dynamic braking status, it can avoid producing over
high pumping voltage in the DC loop.
Recommended specifications are shown in following table:
Inverter model
E550-2S0004
E550-2S0007
E550-2S0015
E550-2S0022
E550-2S0030
E550-2S0040
E550-4T0007
E550-4T0015
E550-4T0022
E550-4T0030
E550-4T0040
Wire specification
Electromagnetic
Adaptive motor
Air circuit breaker
(main loop)
contactor
(KW)
(mm2)
(A)
(A)
0.4
1.5
16
6
0.75
2.5
20
12
1.5
2.5
32
18
2.2
4.0
32
18
3.0
6.0
40
32
4.0
6.0
40
32
0.75
1.0
10
6
1.5
1.5
16
12
2.2
2.5
16
12
3.0
3.0
20
18
4.0
4.0
32
18
E550 Series Universal Low-Power Inverter