Inverter Installation 5
2 Inverter Installation
2.1 Environmental requirements
This series of inverters are wall-mounted products and shall be vertically installed
to facilitate air circulation and heat dissipation. Following attentions shall be paid
for selecting installation environments.
1. The ambient temperature shall be within -1040.
High-temperature and humid places shall be avoided, and
the inverter shall be better placed in a place with humidity
lower than 90% and without frosting.
2. Direct sunshine should be avoided.
3. The inverter should be away from flammable, explosive and
corrosive gas and liquid.
4. The environment should be free of dust, floating fibers and
metal particles.
5. The installation surface should be solid without ventilation.
6. The inverter should be away from electromagnetic
interference sources.
If you have any special installation requirements, please contact us in advance.
See Figure 2-1-A for installation spacing and distance requirement for single
inverter. Enough space should be leaved around the inverter. For installation of
multiple inverters, baffle plate should be applied between inverters to ensure good
heat dissipation, as shown in Figure 2-1-B.
Fan exhaust
50m5m0mm以上
b
! WARNING
1.Refer to the instruction manual before installation
and operation.
2.Do not connect AC power to output terminals UVW.
3.Do not remove any cover while applying power
and at least 10min. after disconnecting power.
4.Securely ground(earth) the equipment.
5500mmmm以上
b
Baffle plate
Figure 2-1-A Installation Spacing Distance Figure 2-1-B Installation of Multiple Inverters
E550 Series Universal Low-Power Inverter
    "